Hydrostatic Testing: Employers must see that all fire extinguishers are tested at the appropriate time | #ESC_LLC #FireExtinguishers #OSHA #NFPA | According to OSHA’s “Portable Fire Extinguishers OSHA Requirements… https://wp.me/p97JNV-16I
An employer must:
◾ Assure that hydrostatic testing is performed by trained persons with suitable testing equipment and facilities. [29 CFR 1910.157(f)(1)]
◾ Assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions [29 CFR 1910.157(f)(2)]:
◦When the cylinder or shell threads are damaged. [29 CFR 1910.157(f)(2)(ii)]
◦When there is corrosion that has caused pitting, including corrosion under removable name plate assemblies. [29 CFR 1910.157(f)(2)(iii)]
◦When the extinguisher has been burned in a fire. [29 CFR 1910.157(f)(2)(iv)]
◦When a calcium chloride extinguishing agent has been used in a stainless steel shell. [29 CFR 1910.157(f)(2)(v)]